City Commission Meeting Room
Before
8-150W Halogen = 9.2A @ 119V
1094.8W
8-100W Floods = 8A @ 120.3V
959.85W
8-200W Inc = 11.5A @ 118.5V
1362.75W
8-70W MH = 6.5A @ 118.1V
767.65W
+ +
16-200W Inc = 25A @ 117.8V
2985.1W
7-100W Inc = 5.8A @ 119V
690.2W
3-75W Inc + 4.0A @ 119.8V
1-300W Inc = 479.2W
8-150W Halogen = 9.2A @ 119V
1094.8W
*No Change*
8-20W CFL = 2.2A @ 120.3V
264.66W
-695.19W
8-20W CFL = 1.9A @ 118.5V
225.15W
-1137.6W
8-70W MH = 6.5A @ 118.1V
767.65W
*No Change*
+ +
16-20W CFL = 3.9A @ 117.8V
459.42W
-2525.68W
7-20W CFL = 2.0A @ 119V
238W
-452.2W
4-20W CFL = 1.0A @ 119.8V
119.8W
-359.4W
62% reduction in total energy consumption in room
80% reduction in energy consumption vs. original bulbs only
Electricity cost = $0.0305/kWh
5.17kW x $0.0305/kWh = $0.1577/h saved
$625.51 / $0.1577/h = 3966 hrs to payback
Bulb life rated @ 6000 hrs